Converters to modbus RTU

Converters to modbus RTU

Usually, one controller is not enough to control large ventilation systems, while the controller doesn't have enough temperature or analogue inputs, analogue or relay outputs. Ouman has successfully solved this problem by developing universal Inputs to Modbus RTU converter, analogue outputs to Modbus RTU converter and other converters. We can create the perfect solution for your ventilation system using one freely programmable controller and by solution needed converters. You could control and monitor your system online via the internet without any problem, just you need to install Modbus RTU to TCP converter. Then you will have a local FTP server, or you could use Ouman cloud (Ouman Flexiot).

8 UNIVERSAL INPUTS TO MODBUS RTU CONVERTER

8 UNIVERSAL INPUTS TO MODBUS RTU CONVERTER

More
8 ANALOGUE OUTPUTS TO MODBUS RTU CONVERTER

8 ANALOGUE OUTPUTS TO MODBUS RTU CONVERTER

More
4 RELAY MODULE TO MODBUS RTU CONVERTER

4 RELAY MODULE TO MODBUS RTU CONVERTER

More
4 TRIAC SWITCHES TO MODBUS RTU CONVERTER

4 TRIAC SWITCHES TO MODBUS RTU CONVERTER

More
UNIVERSAL 16 INPUTS TO MODBUS RTU CONVERTER

UNIVERSAL 16 INPUTS TO MODBUS RTU CONVERTER

More
UNIVERSAL CONVERTER WITH 21 I/O POINTS

UNIVERSAL CONVERTER WITH 21 I/O POINTS

More
UNIVERSAL CONVERTER WITH 32 I/O POINTS

UNIVERSAL CONVERTER WITH 32 I/O POINTS

More

FLEX UI8 - universal 8 inputs to modbus RTU converter

Features

  • Converter FLEX UI8 is using Modbus RTU communication standard with RS-485.
  • Supply voltage 24 VAC/VDC (-10 % ... +20 %) , 50/60 Hz
  • Input signals are 0-10 V or 0/4-20 mA.
  • Input passive sensors - NTC10, NTC1.8, NTC2.2 and NTC20 - Ni 1000 LG, Ni 1000 DIN 43760 - Pt 1000.
  • Protection class IP20
  • DIN rail mounted
Instruction

FLEX AO8 - 8 analogue outputs to modbus RTU converter

Features

  • Converter FLEX AO8 is using Modbus RTU communication standard with RS-485.
  • Supply voltage 24 VAC/VDC (-10 % ... +20 %) , 50/60 Hz
  • Output voltage range 0-10 V
  • Output current 7 mA/output
  • Each output has Auto-Manual switch.
  • Manual position is controlled via potentiometer in each channel separately
  • Protection class IP20
  • DIN rail mounted
Instruction

FLEX DO4 - 4 relay module to modbus RTU converter

Features

  • FLEX DO4-R relay module consists of 4 change-over contact relays.
  • Supply voltage 24 VAC/VDC (-10 % ... +20 %) , 50/60 Hz
  • Change-over contact relay 230 Vac/ 4A or 24Vdc/4A
  • In each relay control it is possible to choose either the automatic control or forced ON or OFF control (ON - AUTO - 0FF).
  • Protection class IP20
  • DIN rail mounted
Instruction

Flex D04-TRS - 4 triac switches to modbus RTU converter erter

Features

  • FLEX DO4-TRS module consists of 4 AC triac switches
  • Supply voltage 24 VAC/VDC (-10 % ... +20 %) , 50/60 Hz
  • Triac load , 24VAC/VDC or 230 VDC, max 1A/output. Potential-free AC switch. DC controls require installation of auxiliary relay
  • In each triac control it is possible to choose either the automatic control or forced ON or OFF control (ON - AUTO - 0FF)
  • Protection class IP20
  • DIN rail mounted
Instruction

FLEX-UI 16 - universal 16 inputs to modbus RTU converter

Features

  • Converter FLEX UI16 is using Modbus RTU communication standard with RS-485.
  • 16 universal inputs (can be configured):
  • Passive sensors (inputs 1…16)
  • Measurement channel accuracy:
  • NTC10 element: +/- 0,1 ºC between -50 ºC…+100 ºC, +/-
  • 0,25 ºC between +100 ºC…+130 ºC
  • Ni1000 element: +/- 1,0 ºC between -50 ºC…+130 ºc
  • PT1000 element: +/- 1,0 ºC between -50 ºC…+130 ºC
  • Also, sensor tolerances and the effect of cables must be considered when calculating total accuracy.
  • Active sensors (inputs 1…16) 0…10 V voltage message, meas. accuracy 1mV Milliampere signal with shunt resistor 0/4-20 mA
  • Contact information (inputs 1…16)
  • Contact voltage 5 Vdc Contact current 0,5 mA
  • Contact resistance max. 1,9 kΩ (closed), min. 11 kΩ (open)
  • Counter inputs (inputs 13…16) Minimum pulse length 30 ms
  • Supply voltage 24 VAC/VDC (-10 % ... +20 %) , 50/60 Hz Protection class IP2
  • DIN rail mounted
Instruction

FLEX-COMBI 21 - universal converter with 21 i/o points

Features

  • Flex Combi 21 is a DIN-rail-attachable I/O device and can be connected RS-485 bus. It has 21 I/O points.
  • 9 Universal inputs (can be configured):
  • Passive sensors (inputs 1…16)
  • Measurement channel accuracy:
  • NTC10 element: +/- 0,1 ºC between -50 ºC…+100 ºC, +/- 0,25 ºC between +100 ºC…+130 ºC
  • Ni1000 element: +/- 1,0 ºC between -50 ºC…+130 ºc
  • PT1000 element: +/- 1,0 ºC between -50 ºC…+130 ºC
  • Also, sensor tolerances and the effect of cables must be considered when calculating total accuracy.
  • Active sensors (inputs 1…16) 0…10 V voltage message, meas. accuracy 1mV Milliampere signal with shunt resistor 0/4-20 mA
  • Contact information (inputs 1…16)
  • Contact voltage 5 Vdc Contact current 0,5 mA
  • Contact resistance max. 1,9 kΩ (closed), min. 11 kΩ (open)
  • Counter inputs (inputs 13…16) Minimum pulse length 30 ms
  • 2 analogue outputs. Output voltage range 0…10 V Output current max. 10 mA
  • 2 change-over contact relay 230 VAC, 6 A
  • 4 normally open contact relay 230 VAC, 6 A
  • 4 triac outputs. Output current together max. 1 A
  • Supply voltage 24 VAC/VDC (-10 % ... +20 %) , 50/60 Hz
  • Protection class IP20
  • DIN rail mounted


Instruction

FLEX-COMBI 32 - universal converter with 32 i/o points

Features

  • Flex Combi 32 is a DIN-rail-attachable I/O device and can be connected RS-485 bus. It has 32 I/O points.
  • 16 Universal inputs (can be configured):
  • Passive sensors (inputs 1…16)
  • Measurement channel accuracy:
  • NTC10 element: +/- 0,1 ºC between -50 ºC…+100 ºC, +/- 0,25 ºC between +100 ºC…+130 ºC
  • Ni1000 element: +/- 1,0 ºC between -50 ºC…+130 ºc
  • PT1000 element: +/- 1,0 ºC between -50 ºC…+130 ºC
  • Also, sensor tolerances and the effect of cables must be considered when calculating total accuracy.
  • Active sensors (inputs 1…16) 0…10 V voltage message, meas. accuracy 1mV Milliampere signal with shunt resistor 0/4-20 mA
  • Contact information (inputs 1…16)
  • Contact voltage 5 Vdc Contact current 0,5 mA
  • Contact resistance max. 1,9 kΩ (closed), min. 11 kΩ (open)
  • Counter inputs (inputs 13…16) Minimum pulse length 30 ms
  • 6 analogue outputs. Output voltage range 0…10 V Output current max. 10 mA
  • 2 change-over contact relay 230 VAC, 6 A
  • 4 normally open contact relay 230 VAC, 6 A
  • 4 triac outputs. Output current together max. 1 A
  • Supply voltage 24 VAC/VDC (-10 % ... +20 %) , 50/60 Hz
  • Protection class IP20
  • DIN rail mounted